| Environmental
Inputs: |
| Number
of Zones: |
8 |
| Zone
Connector: |
Terminal
block |
| Zone
Types: |
N.O./N.C.
contact, 10K thermistor (-20 to 150 degF), and 4-20mA (-10,000
to 10,000) |
| Zone
characteristics: |
10K
to 5V (temperature/contact) or 237 Ohms to ground (4-20mA) |
| A/D
Converter Resolution: |
10 bits ±2
LSB |
| Zone
Protection: |
Gas
discharge tubes, PTC fuses, and fast acting diode clamps |
|
| Microphone: |
| Internal: |
For recording custom voice messages |
| External (optional): |
For listening-in
to on-site sounds and high sound level alarms • Mic Connector: terminal block • Mic Type: Electret Condenser • Mic Impedance: 2.2K |
| LED Indicators: |
(8) Zone Alarms, Sound, Power,
Battery OK, Phone in Use,
Output On, and System On |
| Relay Output: |
2A 120VAC/2A
24VDC - Programmable for automatic or manual switching |
|
| Power
Supply: |
| Power Supply: |
120VAC/12VAC 60Hz 10W wall plug-in
transformer |
| Power Consumption: |
5 Watts |
| Power Protection |
Metal Oxide Varistor |
| Battery Backup: |
12V 2.2 AH sealed gel cell, provides
up to 12 hours of back-up time |
|
| Environmental: |
| Operating Temperature: |
32-122 deg F (0-50 deg C) |
| Operating Humidity: |
0-90% RH non-condensing |
| Storage Temperature: |
32-140 deg F |
|
| Physical: |
| Dimensions: |
12.1"h x 8.0"w x 5.50"d |
| Weight: |
8 lbs. |
| Enclosure: |
Indoor rated ABS Plastic &
Polycarbonate w/clear window door |