The Future of Monitoring


Fully programmable, Monitor unattended or remote sites 24 hours a day. Data Log up to 32,000 records. Communicate by fax, phone, pager, e-mail,
computer or even by Web Page!
Monitor up to eight analog or digital
conditions of your choice (room temperature, outside temperature, humidity,
tank levels, tank temperature, pressure, flow rates, flooding, HVAC controllers
and more), plus power failure.
Select up
to 32 destinations in any combination of phone,
fax, numeric and alphanumeric pager, e-mail, and computer, to receive
alarm messages or status reports. The 2000 is as versatile as you require.
With a single
phone call you can receive a voice status report or data connection for
more detailed information.
Line-seizure function to "grab"
the phone line in an emergency situation.
Built-in data
logging lets you log activity such as trends, usage and other factors
-- up to 32,000 time-stamped records.
Program, view
& monitor input activity in real time via an array of on-screen
input gauges, graphs and bar monitors. Programming is easy point-and-click.
Analyze stored data (up to 32,000
time-stamped records of selected inputs, power and/or battery voltage),
and even process incoming alarms. You choose how often data is sampled,
and how often it's distributed.
Free Microsoft Windows™ compatible
software. Compatible with Windows 3.1,
Windows 95, 98, ME, NT and Windows 2000. Point-and-click programming.
Real-time graphics. 3D charts and graphs for data logging.
Now create updating Web Pages! View monitored data
as a page on your web site.

SENSAPHONE
2000 -- How did you manage without it?
SENSAPHONE 2000
SPECIFICATIONS :
DIALING
PARAMETERS:
Programmable
call list for each input
Alarm acknowledgment: touch tones, callback, or modem
Call progress monitoring: detect dialtone, busy signals,
& ringback
Programmable time between calls: 30 seconds to 60 minutes
DESTINATIONS:
32
destinations: 36-digit telephone numbers, 64 character
E-mail addresses
INPUTS:
1 AC
Power and 8 Universal inputs: normally open/closed
contact, 2.8K/10K thermistor,
4-20mA current loop, or 0-5V analog voltage
10 bit resolution
COMMUNICATION
TYPES:
Voice,
Fax, Modem, Internet E-mail, Numeric Pager, Alpha-Numeric
Pager, Web Page posting.
SPEECH
TECHNOLOGY:
User-recordable
voice for 8 input alarm messages & one ID message
DATALOGGING:
Up
to 32,000 samples (all samples include date and time)
1 second to 200 hour sampling rate
User-programmable channel selection: inputs 1-8, AC
power, & NiCad battery backup
COMMUNICATION
PORTS:
RS232
Programming Port: Used for local programming & set up
DB25 female DCE
38,400 bps
BUILT
IN DATA MODEM:
Data
throughput 14,400 bps
14,400 bps Fax
Protocols: V.32bis, V.32, V.22bis, V.22A/B, V.23, V.21,
Bell 212A &103
LOCAL
INDICATORS:
Inputs
1-8 Alarm Status LEDs
System On LED
Power Alarm LED
Phone LED
Battery OK LED
POWER
REQUIREMENTS:
External transformer
120/220V AC 50/60Hz 10W
(UL listed power supply)
(6) C-cell Rechargeable NiCad batteries (not included)
10 hr battery backup
OPERATING
TEMPERATURE RANGE:
0-50°C
(32-122°F)
HUMIDITY:
0-90%
RH, non-condensing
Size:
12.1"W x 7.2"H x 1.6"D
Shipping